Due to rising supply costs, aging infrastructure along with changing water quality treatment techniques M&M Water Supply Corporation will be increasing our rates effective January 10, 2023.  New rates will be as follows:

METER SIZE:   MONTHLY RATE:
5/8" x 3/4"    $24.00  PLUS $5.50 PER 1000 GALLONS
3/4"  $36.00  PLUS $5.50 PER 1000 GALLONS
1" $60.00  PLUS $5.50 PER  1000 GALLONS
1 1/2"    $120.00 PLUS $5.50 PER  1000 GALLONS
2"  $192.00 PLUS $5.50 PER 1000 GALLONS

               

Various surrounding water system rates:

Angelina WSC       $30.00 base &  $3.50-$8.50/thousand

Four Way SUD      $27.00 base & $4.00/thousand

Hudson                    $16.97 base & $5.87-$13.03/thousand

Etoile WSC             $33.00 base & $3.00/thousand

Woodlawn               $24.00

Central                     $22.00

Angelina County Fresh Water Supply $29.83

Total haloacetic acids maximum contaminant level violation 

The Texas Commission on Environmental Quality (TCEQ) has notified the M&M WSC TX0030026 that the drinking water being supplied to customers has exceeded the maximum contaminant level (MCL) for haloacetic acids (group of five). The U.S. Environmental Protection Agency (U.S. EPA) has established the MCL for haloacetic acids (group of five) to be 0.060 milligrams per liter (mg/l) based on locational running annual average (LRAA), and has determined that it is a health concern at levels above the MCL. Analysis of drinking water in your community for haloacetic acids indicates a compliance value in in quarter one 2020 of 0.061 mg/l for DBP2-01

Haloacetic acids are a group of volatile organic compounds that are formed when chlorine, added to the water during the treatment process for disinfection , reacts with naturally occurring organic matter in the water.

Some people who drink water containing HAA5 in excess of the MCL over many years may may have an increased risk of getting cancer.

You do not need to use an alternative water supply. However, if you have health concerns, you may want to talk to your doctor to get more information about how this may affect you.

We are taking the following actions to address this issue:

  1. Proper training of employees
  2. Enhanced flushing program to reduce water age in distribution system
  3. Pilot study of various treatment techniques used to mitigate HAA5 formation.

Please share this information with all people who drink this water, especially those who may not have received this notice directly (i.e., people in apartments, nursing homes, schools, and businesses). You can do this by posting this notice in a public place or distributing copies by hand or mail.  

TTHM maximum contaminant level violation

 The Texas Commission on Environmental Quality (TCEQ) has notified the M&M WSC TX0030026 that the drinking water being supplied to customers has exceeded the maximum contaminant level (MCL) for total trihalomethanes. The U.S. Environmental Protection Agency (U.S. EPA) has established the MCL for total trihalomethanes to be 0.080 milligrams per liter (mg/l) based on locational running annual average (LRAA), and has determined that it is a health concern at levels above the MCL. Analysis of drinking water in your community for total trihalomethanes indicates a compliance value in in quarter 0ne 2020 of 0.090 mg/l for DBP2-01 and 0.082 for dbp2-02.

Trihalomethanes are a group of volatile organic compounds that are formed when chlorine, added to the water during the treatment process for disinfection , reacts with naturally occurring organic matter in the water.

Some people who drink water containing trihalomethanes in excess of the MCL over many years may experience problems with their liver, kidney, or central nervous system, and may have an increased risk of getting cancer.

You do not need to use an alternative water supply. However, if you have health concerns, you may want to talk to your doctor to get more information about how this may affect you.

We are taking the following actions to address this issue:

  1. Proper training of employees
  2. Enhanced flushing program to reduce water age in distribution system
  3. Pilot study of various treatment techniques used to mitigate TTHM formation.

Please share this information with all people who drink this water, especially those who may not have received this notice directly (i.e., people in apartments, nursing homes, schools, and businesses). You can do this by posting this notice in a public place or distributing copies by hand or mail.  

As your local water utility provider, we strive to keep you continually updated on all matters related to your water service. If you do not find the information you need, please contact our office and we will gladly assist you!

TTHM MAXIMUM CONTAMINANT LEVEL VIOLATION

The Texas Commission on Environmental Quality (TCEQ) has notified the M&M WSC TX0030026 that the drinking water being supplied to customers has exceeded the maximum contaminant level (MCL) for...